MOONS NPSUGMDHB Wireless Node Controller Owner’s Manual

MOONS NPSUGMDHB Wireless Node Controller Owner’s Manual

MOONS-LOGO

MOONS NPSUGMDHB Wireless Node Controller

MOONS-NPSUGMDHB-Wireless-Node-Controller-PRODUCT

Specyfikacje

  • Customer’s Part Number:
  • MOONS’ Part Number: 4696355000211
  • Model: NPSUGMDHB
  • Nr części: A8768

Zastrzega się możliwość zmian bez powiadomienia

OPIS

  • The Wireless Node Controllers can be installed in the lighting control box, lamp chamber or installed self-contained under eaves or other sheltered areas due to the solid metal enclosure.
  • It is very small size and excellent waterproof.
  • It can automatically identify different types of LED driver, such as 0-10V, DALI-2/D4i and DMX(RDM).
  • Supports 2 channels 0-10V for color temperature adjustment.
  • Supports RGBW color.
  • Supports dynamic scenes and animations.
  • It communicates with the gateway through a WPAN (Sub-GHz).
  • Self-building and self-healing MESH Network.
  • The sensor interface supports sensor access with digital and analog outputs.

CECHY

  • Objętość wejściowatage:12-30VDC.
  • Power consumption: < 1W.
  • Wireless communication: IEEE 802.15.4-915MHz.
  • Automatically identify dimming mode.
  • DMX(RDM) master, up to 6 loads.
  • DALI-2/D4i Single-Master Controller, up to 6 loads.
  • 2 channels of 0-10V Dimmer, up to 4 loads each channel.
  • RGBW color support
  • Dynamic scenes and animations
  • 1 channel of sensor sampwejście.
  • Save several dimming plans.
  • Firmware upgrade: OTA.
  • Embedded communication encryption mechanism.
  • Radio frequency certification: FCC
  • Warranty: 5years.

MOONS-NPSUGMDHB-Wireless-Node-Controller- (1)

CECHY CHARAKTERYSTYCZNE

 CHARAKTERYSTYKA ELEKTRYCZNA
At 20 ℃, 50% RH, 100Kpa conditions.

Parametr Warunki testowe Min Typ Maksymalnie Jednostka
Objętość wejściowatagi (1) 12 24 30 VDC
Pobór mocy 0.2 / 1.0 W
ściemnianie głośnościtage DA, DB -6 / 22.5 V
DMX voltage DA, DB to GND -3.3 / +3.3 V
DMX current DA to DB short / / 70 mA
DMX Baud rate / 250 / Kbps
DALI BUS voltage DA to DB 0 / 20.5 V
DALI high level voltage DA to DB 9.5 / 22.5 V
DALI low level voltage DA to DB -6.5 / 6.5 V
DALI BUS current Not transmitting Transmitter sink 0.5 / 2 mA
Objętość wyjściowa 0-10 Vtagi (2) DA, DB to GND 0 / 11 V
0-10V current Każdy kanał / / 10 mA
Czujnik Samplottage 0 / 11 V
WPAN transmission distance / / 300 m
WPAN band 904 / 926 MHz
WPAN receiver sensitivity -100 / / dBm
WPAN transmitter power / / 20.5 dBm

Notatka:

  1. In the case of DALI-2/D4i mode, the input voltage needs to be higher than the DALI BUS voltage.
  2. Gdy wejściowa objętośćtage is 12V, 0-10V can output 10V at most; When the output voltage is > 12V, 0-10V can output 11V.

Warunki pracy

Parametr Warunki testowe Min Typ Maksymalnie Jednostka
Temperatura pracy -40 / +70 °C
Temperatura przechowywania Dry indoor, well-ventilated place -40 / +85 °C
Wilgotność względna Bez szronu 10 / 95 %
Wibracja / 1 / G
Gwarancja 5 / / Lata
Ingress protection classification Nie zainstalowano IP66 / /
Łatwopalność UL94-V0 / /

Kompatybilność elektromagnetyczna

Typ Standard Poziom testowy
Odporność na wyładowania elektrostatyczne IEC61000-4-2 Poziom 2
RFEMS IEC61000-4-3 Poziom 2
Electrical fast transient burst immunity IEC61000-4-4 Poziom 4
Odporność na udary IEC61000-4-5 Poziom 2
Conducted disturbances induced by RF field immunity IEC61000-4-6 Poziom 3
Odporność na pole magnetyczne o częstotliwości sieciowej IEC61000-4-8 Poziom 3

Orzecznictwo

Typ Standard
Electromagnetic interference characteristics certification FCC ID: 2BRS4-NPSUGMDHB
Energia FCC 47 CFR Part15 B Class B; FCC 47 CFR Part15 C (915M WPAN); DLC-indoor/outdoor
Operatywność DALI-2/D4i: IEC62368-PART 101; IEC62368-PART 103; IEC62368-PART 251; IEC62368-PART 252; IEC62368-PART 253; IEC62368-PART 351; (Type D Single-Master Controller)

Dane mechaniczne

Wymiary
Dimensions are provided in the diagrams above.

MOONS-NPSUGMDHB-Wireless-Node-Controller- (2)

Antena

 Akcesoria opcjonalne MOONS-NPSUGMDHB-Wireless-Node-Controller- (3)

ETYKIETA 

MOONS-NPSUGMDHB-Wireless-Node-Controller- (4)

Product barcode information:

  • The last 8 digits of SN represent the communication address of the product.
  • A” indicates that this product operates in the American frequency band;
  • The QR code shows the product’s communication address.

MOONS-NPSUGMDHB-Wireless-Node-Controller- (5)

Opisy funkcji

Interfejsy

Nazwa Kolor Opis
MOC Brązowy Power supply input DC +
GND Czarny Power supply input DC -; Dimming/sensor Common port
TRANSDUKTOR Niebieski czujnikample input +
DCOM Żółty Dimming/sensor Common port; DMX shielding
DA Fioletowy 0-10V Dimming+ channel 1; DMX data +; DALI bus +
DB Różowy 0-10V Dimming+ channel 2; DMX data -; DALI bus –
ANTENA Czarny Sub-GHz communication antenna interface

WPAN Module

  • Communicate with the Gateway. Transfer various instructions, such as: dimming command, upload power metering data, set parameters and query telemetries accordingly and so on.
  • Wireless communication: IEEE 802.15.4-Sub-GHz.
  • Embedded communication encryption mechanism.

Ściemnianie
Once the device is powered up, it will automatically identify the dimming mode (DALI-2/D4i / DMX(RDM) /0-10V) of the connected load. After recognition, it will automatically report its own running dimming mode and perform necessary operation in this way.

Ogłoszenie: To achieve perfect recognition of the dimming type, it is recommended that the controller and the LED driver be powered on simultaneously, or the controller be powered on later than the LED driver.

Ściemnianie 0-10V

  • If it is identified as 0-10V dimmer, it can support 2-channel independent 0-10V dimming, which can support adjusting the color temperature (tunable white LED driver and software configuration are required).
  • The DIM-TO-OFF LED drivers should be used; the LED drivers’ output will turn off once the dimming voltage jest < 0.5V.
  • Support positive and negative logic dimming (configuration required).
  • If each channel is connected to multiple LED drivers, the maximum output current of each channel is 10mA, and if the load current is >10mA, the output voltage will be not accurate.

Ogłoszenie: Gdy wejściowa objętośćtage is 12V, 0-10V can output 10V at most; When the output voltage is > 12V, 0-10V can output 11V.

DMX(RDM)

  • If identified as a DMX(RDM) master, it can support up to 6 loads (maximum 3 slots for each load) and can be automatically addressed to support RDM instructions.
  • 4 loads are recommended.

MOONS-NPSUGMDHB-Wireless-Node-Controller- (6)

DALI-2/D4i

  • If identified as a DALI-2/D4i Single-Master Controller, up to 6 loads (one address for each load) can be supported, supporting IEC62386-101/103/251/252/253/351 (TYPE D).
  • 4 loads are recommended.

Ogłoszenie:

  • At least one of the DALI-2/D4i LED drivers needs to be set to supply power to the DALI bus.
  • Maximum of 6 DALI-2/D4i LED Drivers, any DALI-2/D4i LED Drivers >4 will need the power supply disabled
  • In the case of DALI-2/D4i mode, the input voltage needs to be higher than the DALI BUS voltage.

Wejście czujnika

  • 1 channel of sensor input interface.
  • Sensors with 0-10V output can be accessed.
  • Passive digital output can be accessed.
  • Sensors must be configured in software before it is functional in system.

Kontrolki świetlne

Kolor Status Wskazać
CZERWONY WYŁĄCZONY Brak zasilania
CZERWONY ON Initial process or some failure/error happened
CZERWONY Błysk Trying to identify the dimming

Ogłoszenie: 

  1.  Purple light indicates that the communication between node controller and LED driver is lost. This might be due to use wrong LED driver or LED driver is not power on or wiring error (for example the reverse connection of the DMX bus). Please check the wiring connection or the power-on status of the LED driver, and then re-power the node controller.

INSTALACJA

For DALI-2/D4i applications with sensor MOONS-NPSUGMDHB-Wireless-Node-Controller- (7)

For DMX(RDM) applications with sensor  MOONS-NPSUGMDHB-Wireless-Node-Controller- (8)

For 0-10V Dim to off applications with sensor  MOONS-NPSUGMDHB-Wireless-Node-Controller- (9)

 For 0-10V Tunable white applications with sensor  MOONS-NPSUGMDHB-Wireless-Node-Controller- (10)

 Recommended installation of antenna interface  MOONS-NPSUGMDHB-Wireless-Node-Controller- (11)

 Recommended installation of M18 Antenna  MOONS-NPSUGMDHB-Wireless-Node-Controller- (12)

ZAMAWIANIE

OPIS KOD ZAMÓWIENIA
NPSUGMDHB3in1 Wireless Node Controller (without Antenna) 4696355000211
Straight Whip Antenna(RP-SMA connect) 4741135000149(Optional accessories)
Right Angle Whip Antenna(RP-SMA connect) 4741135000150(Optional accessories)
M18 Antenna(RP-SMA connect) 4741135000153(Optional accessories)

Oświadczenie FCC

To urządzenie jest zgodne z częścią 15 przepisów FCC. Jego działanie podlega następującym dwóm warunkom:

  1. To urządzenie nie może powodować szkodliwych zakłóceń i
  2. Urządzenie musi akceptować wszelkie odbierane zakłócenia, w tym zakłócenia mogące powodować niepożądane działanie.

Ostrożność: Użytkownik jest ostrzegany, że wszelkie zmiany lub modyfikacje, które nie zostały wyraźnie zatwierdzone przez stronę odpowiedzialną za zgodność, mogą spowodować unieważnienie prawa użytkownika do korzystania ze sprzętu.

Notatka:To urządzenie zostało przetestowane i uznane za zgodne z ograniczeniami dla urządzeń cyfrowych klasy B, zgodnie z częścią 15 przepisów FCC.

Te limity mają na celu zapewnienie rozsądnej ochrony przed szkodliwymi zakłóceniami w instalacji mieszkalnej. Ten sprzęt generuje zastosowania i może emitować energię o częstotliwości radiowej i, jeśli nie jest zainstalowany i używany zgodnie z instrukcją, może powodować szkodliwe zakłócenia w komunikacji radiowej. Nie ma jednak gwarancji, że zakłócenia nie wystąpią w konkretnej instalacji. Jeśli ten sprzęt powoduje szkodliwe zakłócenia w odbiorze radia lub telewizji, co można ustalić, wyłączając i włączając urządzenie, zachęca się użytkownika do podjęcia próby skorygowania zakłóceń za pomocą jednego lub więcej z następujących środków:

  • Zmiana orientacji lub położenia anteny odbiorczej.
  • Zwiększ odległość między urządzeniem i odbiornikiem.
  • Podłącz urządzenie do gniazdka w innym obwodzie niż ten, do którego podłączony jest odbiornik.
  • Aby uzyskać pomoc, należy zwrócić się do sprzedawcy lub doświadczonego technika radiowo-telewizyjnego.

Aby zachować zgodność z wytycznymi FCC dotyczącymi ekspozycji na fale radiowe, urządzenie to należy zainstalować i obsługiwać z zachowaniem minimalnej odległości 20 cm między radiatorem a ciałem. Należy używać wyłącznie dołączonej anteny.

CUSTOMER’S APPROVAL STAMP
Please sign back after your approval. The specifications will come into force when we receive purchase order.

Plik DWG. CHK. STANDARD ZAŁ.
       

Zastrzega się możliwość zmian bez powiadomienia
© 2024 MOONS’. All rights reserved. All content contained herein is subject to change without prior notice. More product documentation and MOONS’ terms and conditions are available at https://www.moonsindustries.com

History Version 

Obrót silnika. Data Zawartość Nr EKO Plik DWG. CHK. OKR.
 A0  2025-09-15  Pierwsza wersja  Jiabin.gu  Wanghui.yan  Yiping.lai
  A1   2025-11-14 Change the model; modify the antenna;modify the label.   ECO25-1265DE   Jiabin.gu   Wanghui.yan   Yiping.lai
 A2  2026-01-13 Correct the line lengths in the mechanical drawings  ECO26-0037DE  Jiabin.gu  Jackie.gu  Yiping.lai

Dokumenty / Zasoby

PDF thumbnailNPSUGMDHB Wireless Node Controller
Owner's Manual · 2BRS4-NPSUGMDHB, 2BRS4NPSUGMDHB, 4696355000211, A8768, NPSUGMDHB Wireless Node Controller, NPSUGMDHB, Wireless Node Controller, Node Controller, Controller

Odniesienia

Zadaj pytanie

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Zadaj pytanie

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.