YORK 3 Ton, 1/8 Inch El, R-410A

Instrukcja obsługi zaworu rozprężnego termicznego York

Model: 3 Ton, 1/8 Inch El, R-410A

1. Wprowadzenie

This manual provides essential information for the proper installation, operation, and maintenance of the York Thermal Expansion Valve (TXV). This genuine OEM part is designed to ensure optimal performance and reliability in compatible R-410A refrigerant systems. Please read this manual thoroughly before proceeding with any procedures.

2. Koniec produktuview

The York Thermal Expansion Valve is a critical component in refrigeration and air conditioning systems. Its primary function is to regulate the flow of liquid refrigerant into the evaporator while maintaining a constant superheat at the evaporator outlet. This specific model is rated for 3-ton capacity and features a 1/8 inch equalizer line connection, designed for use with R-410A refrigerant.

York Thermal Expansion Valve with copper tubing and mounting bracket

An image showing the York Thermal Expansion Valve, featuring its brass body, coiled copper sensing bulb capillary tube, and a metal mounting bracket with a screw. The valve is designed for R-410A refrigerant systems.

3. Informacje dotyczące bezpieczeństwa

4. Konfiguracja i instalacja

Proper installation is crucial for the efficient operation of the TXV. This procedure should only be carried out by a certified HVAC professional.

  1. Dekompresja układu: Ensure the refrigeration system is completely depressurized and evacuated before beginning installation.
  2. Umiejscowienie zaworu: Install the TXV in the liquid line just upstream of the evaporator. Ensure the flow direction arrow on the valve body matches the refrigerant flow.
  3. Brazing Connections: Use appropriate brazing techniques and materials for R-410A systems. Protect the valve body from excessive heat during brazing to prevent internal damage.
  4. Equalizer Line Connection: Connect the 1/8 inch equalizer line from the TXV to the suction line, typically downstream of the evaporator and sensing bulb.
  5. Montaż żarówki czujnikowej: Securely attach the sensing bulb to the suction line at the evaporator outlet. Ensure good thermal contact by cleaning the pipe surface and using a clamp. Insulate the bulb to prevent ambient temperature interference.
  6. Badania szczelności: After installation, perform a thorough leak test on all connections using an appropriate leak detector.
  7. Ewakuacja i ładowanie: Evacuate the system to a deep vacuum and then charge with the correct amount of R-410A refrigerant according to the system manufacturer's specifications.

5. Zasady działania

The Thermal Expansion Valve operates by balancing forces to control refrigerant flow. The primary forces are:

When the superheat at the evaporator outlet increases, the sensing bulb temperature rises, increasing its internal pressure. This pressure overcomes the combined evaporator and spring pressures, opening the valve further to allow more refrigerant into the evaporator. Conversely, if superheat decreases, the bulb pressure drops, causing the valve to close slightly, reducing refrigerant flow. This continuous modulation ensures efficient heat transfer and protects the compressor from liquid slugging.

6. Konserwacja

The York TXV is designed for long-term reliability. Regular system maintenance by a qualified technician is recommended to ensure its continued optimal performance.

7. Rozwiązywanie Problemów

If the refrigeration system is not performing as expected, the TXV may be a contributing factor. Troubleshooting should be performed by a qualified technician.

ObjawMożliwa przyczynaDziałanie
High Superheat, Low Suction PressureTXV stuck closed or restricted; low refrigerant charge; dirty evaporator coil.Check refrigerant charge; clean evaporator; inspect TXV for blockage or failure.
Low Superheat, High Suction Pressure (Liquid Slugging)TXV stuck open; sensing bulb loose or uninsulated; oversized TXV.Re-secure/insulate sensing bulb; inspect TXV for failure; verify correct TXV sizing.
Fluctuating Superheat/Suction PressureMoisture in system; non-condensables; improper sensing bulb contact.Evacuate and recharge system; check sensing bulb installation.
External Refrigerant LeakLoose connections; damaged valve body or capillary tube.Locate and repair leak; replace TXV if damaged.

Always consult with a professional HVAC technician for accurate diagnosis and repair of TXV-related issues.

8. Specyfikacje

9. Informacje o gwarancji

This York Thermal Expansion Valve is a genuine OEM part. Warranty coverage for this product is typically provided by the manufacturer, York, against defects in materials and workmanship. Specific warranty terms, duration, and conditions may vary. Please retain your proof of purchase and contact your seller or the official York customer support for detailed warranty information and claims procedures.

10. Informacje o pomocy technicznej

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact:

Powiązane dokumenty - 3 Ton, 1/8 Inch El, R-410A

Przedview Instrukcja montażu i konserwacji urządzeń dachowych YORK Sun Premier o udźwigu 25–50 ton
Szczegółowy przewodnik instalacji i konserwacji urządzeń dachowych YORK Sun Premier o udźwigu 25–50 ton (RTU). Obejmuje specyfikacje urządzeń, procedury instalacji, wymagania elektryczne, protokoły bezpieczeństwa i rutynową konserwację w celu zapewnienia optymalnej wydajności.
Przedview Poradnik inżynieryjny dla jednostek dachowych YORK 50-65 ton w jednym pakiecie
Poznaj jednostki dachowe YORK 50-65 ton Single Package (seria YPAL) w tym kompleksowym przewodniku inżynieryjnym. Poznaj funkcje, specyfikacje i szczegóły zastosowań wydajnych rozwiązań chłodniczych i grzewczych, w tym kompatybilność z czynnikiem chłodniczym R-410A.
Przedview Przewodnik techniczny YORK Sun Choice HV13 do HV25
Kompleksowy przewodnik techniczny dotyczący jednostek HVAC YORK Sun Choice HV13 do HV25, zawierający szczegółowe dane techniczne, funkcje, opcje, dane dotyczące wydajności i informacje elektryczne przeznaczone do zastosowań komercyjnych.
Przedview Chłodziarka spiralna chłodzona powietrzem YORK YLAA typu B: Karta opakowania i informacje dotyczące bezpieczeństwa
Niniejsza ulotka dotycząca chłodziarki spiralnej chłodzonej powietrzem YORK YLAA typu B zawiera podstawowe informacje prawne, gwarancyjne, dotyczące bezpieczeństwa i instalacji urządzeń wykorzystujących czynniki chłodnicze R-410A i R-454B.
Przedview Instrukcja serwisowa klimatyzatora YORK 15-25 ton w pojedynczym pakiecie gazowo-elektrycznym i elektryczno-elektrycznym
Kompleksowa instrukcja obsługi, konserwacji i serwisu klimatyzatorów YORK o udźwigu 15–25 ton (gazowo-elektrycznych i elektryczno-elektrycznych). Obejmuje ona bezpieczeństwo, obsługę systemu, procedury konserwacyjne, rozwiązywanie problemów oraz informacje dla właściciela.
Przedview Instrukcja obsługi falownika ściennego YORK Altair High Wall Inverter R-410A 60Hz 16SEER
Instrukcja obsługi klimatyzatora ściennego YORK Altair High Wall Inverter (R-410A, 60 Hz, 16 SEER) obejmująca kwestie instalacji, obsługi, konserwacji, środków ostrożności i rozwiązywania problemów.