Simplex 4098-9733

Instrukcja obsługi czujnika ciepła Simplex 4098-9733

Model: 4098-9733 | Brand: Simplex

1. Wprowadzenie

This manual provides essential information for the proper installation, operation, and maintenance of the Simplex 4098-9733 Heat Detector. Adherence to these instructions is crucial for ensuring the detector's optimal performance and compliance with safety standards.

1.1 Cel tej instrukcji

The purpose of this document is to guide qualified personnel through the necessary steps for deploying and managing the Simplex 4098-9733 Heat Detector within a fire alarm system. It covers technical specifications, installation procedures, operational guidelines, and maintenance recommendations.

1.2 Ważne informacje dotyczące bezpieczeństwa

Zawsze przestrzegaj następujących środków ostrożności:

2. Koniec produktuview

The Simplex 4098-9733 is a fixed-temperature heat detector designed to provide reliable fire detection by responding to a specific temperature threshold. It is typically integrated into a larger fire alarm system.

2.1 Główne cechy

2.2 składniki produktu

The Simplex 4098-9733 Heat Detector consists of the main detector head and typically requires a compatible mounting base (sold separately) for installation into a fire alarm circuit.

A box filled with multiple red Simplex 4098-9733 heat detectors, each individually packaged in clear plastic.

This image displays a cardboard box containing numerous Simplex 4098-9733 heat detectors. Each detector is red, circular, and encased in clear plastic packaging, indicating new, unused units ready for installation.

3. Konfiguracja i instalacja

3.1 przed instalacją

3.2 Montaż detektora

The 4098-9733 detector requires a compatible mounting base (e.g., Simplex 4098-9792, 4098-9789, or similar, sold separately) for proper installation.

  1. Turn off all power to the fire alarm control panel and associated circuits.
  2. Mount the detector base securely to a standard electrical box or directly to the ceiling/wall according to local codes.
  3. Connect the wiring from the fire alarm control panel to the appropriate terminals on the detector base (refer to the wiring diagram below).
  4. Align the detector head with the mounting base and rotate clockwise until it locks into place.
  5. Restore power to the fire alarm control panel and test the detector.

3.3 Okablowanie

Proper wiring is critical for the detector's functionality. Refer to the specific wiring diagram provided with your detector base and fire alarm control panel documentation. A typical wiring configuration for a two-wire system is as follows:

Typical Wiring Connections (Consult Base Manual for Specifics)
TerminalOpis
1Signal Line In (+)
2Signal Line Out (+)
3Signal Line In/Out (-)
4Remote Annunciator (if applicable)

4. Instrukcja obsługi

4.1 Normalna praca

Under normal conditions, the Simplex 4098-9733 Heat Detector continuously monitors the ambient temperature. It draws minimal current from the fire alarm control panel and typically has an indicator LED that may flash periodically to confirm normal operation (check your specific base and panel documentation for LED behavior).

4.2 Stan alarmowy

When the ambient temperature at the detector reaches or exceeds 135°F (57°C), the detector will activate. This activation sends a signal to the fire alarm control panel, initiating the alarm sequence (e.g., sounding alarms, notifying monitoring stations). The detector's LED will typically illuminate steadily to indicate its alarm state.

Upon an alarm, follow your facility's emergency procedures immediately. Do not attempt to reset the detector until the cause of the alarm has been identified and resolved.

5. Konserwacja

Regular maintenance is essential to ensure the continued reliability and proper functioning of your heat detector.

5.1 Regularna kontrola

5.2 Czyszczenie

If dust or debris is visible, clean the exterior of the detector using a soft, dry cloth. Do not use cleaning sprays or solvents directly on the detector. For more thorough cleaning, consult a qualified fire alarm technician.

5.3 Testowanie

Heat detectors should be tested periodically by qualified personnel in accordance with NFPA 72 and local fire codes. Testing typically involves applying a controlled heat source to the detector to verify its activation at the rated temperature. Never use an open flame for testing.

6. Rozwiązywanie Problemów

This section addresses common issues that may arise with the Simplex 4098-9733 Heat Detector. For complex problems, contact a qualified fire alarm technician.

ProblemMożliwa przyczynaRozwiązanie
Detector not responding to heat testIncorrect wiring, faulty detector, insufficient heat applied, incompatible base.Verify wiring connections. Ensure adequate heat is applied during testing. Check detector compatibility with base and panel. Replace detector if faulty.
Fałszywe alarmyDetector located near heat source (e.g., furnace, oven), environmental factors.Relocate detector away from heat sources. Ensure proper ventilation. Consult installation guidelines for appropriate placement.
System trouble signalWiring fault, detector not seated correctly, power issue.Check all wiring connections. Ensure detector is securely twisted onto its base. Verify power supply to the fire alarm control panel.

7. Specyfikacje techniczne

The following table outlines the technical specifications for the Simplex 4098-9733 Heat Detector:

SpecyfikacjaSzczegół
Numer modelu4098-9733
Typ czujnikaFixed Temperature Heat Detector
Temperatura aktywacji135°F (57°C)
Typ alarmuAudible (via control panel)
Wilgotność roboczaDo 90% bez kondensacji
Źródło zasilaniaPowered by Fire Alarm Control Panel (not battery operated)
TworzywoMetal, Plastik
KolorCzerwony, biały
Waga przedmiotu3.2 uncji (w przybliżeniu)
Wymiary produktu5 x 5 x 3 cala (w przybliżeniu)
UPC643485652892

8. Gwarancja i wsparcie

8.1 Informacje o gwarancji

Simplex products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the official warranty statement provided with your purchase or contact Simplex customer service. Keep your proof of purchase for warranty claims.

8.2 Wsparcie techniczne

For technical assistance, troubleshooting beyond this manual, or to inquire about service, please contact your authorized Simplex distributor or a qualified fire alarm service provider. Ensure you have the model number (4098-9733) and any relevant system information available when seeking support.

Powiązane dokumenty - 4098-9733

Przedview Czujniki analogowe Simplex TrueAlarm: Arkusz danych fotoelektrycznych i cieplnych
Comprehensive datasheet for Simplex TrueAlarm Analog Sensors, detailing photoelectric and heat models, standard bases, and accessories. Includes features, intelligent data evaluation, sensor specifications, mounting references, and product selection charts for fire alarm systems.
Przedview Simplex 4098-9019 IDNet Adresowalny Detektor Belkowy Przewodnik Po Okablowaniu i Programowaniu FACP
Kompleksowy przewodnik po okablowaniu i programowaniu systemu adresowalnych czujek wiązkowych Simplex 4098-9019 IDNet z centralami sygnalizacji pożarowej Simplex (FACP). Obejmuje kompatybilność, specyfikację elektryczną, adresowanie i obsługę centrali.
Przedview Instrukcja obsługi detektorów, czujników i baz Simplex 4098
This application manual provides comprehensive information on the proper use and installation of Simplex 4098 series detectors, sensors, and bases within fire alarm systems. It covers principles of operation, placement guidelines, compatibility, testing procedures, and troubleshooting for these critical fire safety components.
Przedview Simplex 4008/4006-9801 Expansion Power Supply (EPS) Installation Guide
Installation instructions for the Simplex 4008/4006-9801 Expansion Power Supply (EPS), detailing mounting, panel interconnections, NAC wiring, auxiliary power, and NAC ratings for fire alarm systems.
Przedview Simplex 2098 Series Smoke Detectors: Installation Instructions and Specifications
This document provides installation instructions, technical specifications, and wiring diagrams for Simplex 2098-9201, 2098-9202, 2098-9203, 2098-9208, and 2098-9576 smoke detectors, covering both photoelectric and ionization types. It details general information, special considerations for installation, applications, maintenance, testing procedures, and limitations of smoke detection technology.
Przedview Alarm przeciwpożarowy Simplex 4010: Instrukcja instalacji, obsługi i programowania
Kompleksowy przewodnik dotyczący instalacji, obsługi i programowania systemu alarmowego Simplex 4010. Obejmuje systemview, okablowanie, konfiguracja, diagnostyka i rozwiązywanie problemów.