Fluke I1000S Large AC Current Probe Instruction Manual

Model: I1000S

1. Wprowadzenie

The Fluke I1000S is a high-performance clamp-on AC current probe designed for accurate current measurements in industrial and power environments. It is ideal for use with oscilloscopes to analyze distorted current waveforms and harmonics, providing precise data without the need to break into the circuit.

Fluke I1000S Large AC Current Probe

Image 1.1: The Fluke I1000S Large AC Current Probe, showing its red clamp jaws, gray body with a selector switch, and the attached coaxial cable with a BNC connector.

This manual provides essential information for the safe and effective operation, maintenance, and troubleshooting of your Fluke I1000S AC Current Probe.

2. Główne cechy

3. Konfiguracja

Before using the Fluke I1000S, ensure all connections are secure and the probe is clean.

  1. Połącz się z oscyloskopem: Connect the BNC connector of the probe's coaxial cable directly to the input channel of your oscilloscope. Ensure the connection is firm.
  2. Connect to Multimeter (Optional): If using with a multimeter, attach the optional PM9081/001 BNC/Banana adapter to the probe's BNC connector, then connect the banana plugs to the appropriate input jacks on your multimeter.
  3. Wybierz zakres: Use the selector switch on the probe body to choose the appropriate current range (10 A, 100 A, or 1000 A) based on the expected current of the circuit being measured.
  4. Włączanie: Ensure your connected measurement device (oscilloscope or multimeter) is powered on and configured for current measurement.

4. Instrukcja obsługi

Follow these steps for accurate current measurement:

  1. Bezpieczeństwo przede wszystkim: Always ensure the circuit is de-energized or appropriate safety precautions are taken before clamping the probe around a conductor. Observe the CAT III, 600 V safety rating.
  2. Otwórz klasęamp: Press the lever on the probe to open the clamp szczęki
  3. Encircle Conductor: Carefully place the open jaws around a single conductor carrying the AC current you wish to measure. Ensure the jaws close completely around the conductor. Do not clamp around multiple conductors if you intend to measure the current in only one.
  4. Wybierz zakres: Verify that the selected range on the probe (10 A, 100 A, or 1000 A) is suitable for the expected current. Start with a higher range if unsure to prevent overloading.
  5. Odczyt pomiaru: Observe the current reading on your connected oscilloscope or multimeter. The probe outputs are 100 mV/A, 10 mV/A, and 1 mV/A for the 10 A, 100 A, and 1000 A ranges respectively. Adjust your measurement device's settings as needed to interpret the output correctly.
  6. Odłączyć: After measurement, open the clamp jaws and remove the probe from the conductor. Disconnect the probe from your measurement device.

Notatka: The passive filter helps in obtaining clean waveforms, especially for distorted signals and harmonics. Ensure proper grounding of your oscilloscope for optimal performance.

5. Konserwacja

Proper maintenance ensures the longevity and accuracy of your Fluke I1000S probe.

6. Rozwiązywanie Problemów

If you encounter issues with your Fluke I1000S probe, consider the following common problems and solutions:

ProblemMożliwa przyczynaRozwiązanie
Brak czytania lub czytanie nieregularne
  • Incorrect range selected.
  • Probe jaws not fully closed.
  • Uszkodzony kabel lub złącze.
  • Conductor not properly centered.
  • Measurement device not configured correctly.
  • Select appropriate current range.
  • Ensure jaws are completely closed around a single conductor.
  • Inspect cable and connector for damage; replace if necessary.
  • Reposition the probe to center the conductor.
  • Check oscilloscope/multimeter settings (e.g., input impedance, scaling).
Noisy or distorted waveform on oscilloscope
  • Zewnętrzne zakłócenia elektromagnetyczne.
  • Improper grounding of oscilloscope.
  • High frequency noise not fully filtered.
  • Move probe away from strong magnetic fields.
  • Ensure oscilloscope is properly grounded.
  • Verify the passive filter is functioning; if issues persist, contact support.

If the problem persists after attempting these solutions, please contact Fluke customer support.

7. Specyfikacje

ParametrWartość
ModelI1000S
Nominal Current Ranges10 A, 100 A, 1000 A
Continuous Current Range0.1 A - 10 A, 0.1 A - 100 A, 1 A - 1000 A
Maximum Non-Destructive Current2000 A
Najniższy mierzalny prąd0.1 A
Basic Accuracy (48-65 Hz)1% + 1 A
Usable Frequency Range5 Hz - 100 kHz
Poziomy wyjściowe100 mV/A (10A range), 10 mV/A (100A range), 1 mV/A (1000A range)
Ocena bezpieczeństwaKAT III, 600 V
Typ połączeniaReinforced Coaxial Cable with Insulated BNC Connector
Waga przedmiotu6.3 uncji
Wymiary produktu3.74 x 1.97 x 0.47 cala

8. Informacje o gwarancji

The Fluke I1000S Large AC Current Probe comes with a roczna gwarancja from the date of purchase. This warranty covers defects in materials and workmanship under normal use. For warranty service, please retain your proof of purchase and contact Fluke customer support.

The warranty does not cover damage resulting from misuse, accident, modification, contamination, neglect, or damage caused by operating conditions outside the product's specified limits.

9. Wsparcie i kontakt

For technical assistance, product inquiries, or warranty claims, please contact Fluke customer support:

When contacting support, please have your product model (I1000S) and serial number (if applicable) ready.

Powiązane dokumenty - I1000S

Przedview Multimetr Fluke 110 True-RMS: dane techniczne i funkcje
Szczegółowe specyfikacje i funkcje kompaktowego multimetru Fluke 110 True-RMS, zaprojektowanego do precyzyjnej instalacji elektrycznej i diagnostyki. Zawiera dane dotyczące dokładności, klas bezpieczeństwa i dołączone akcesoria.
Przedview Fluke 381 Zdalny wyświetlacz True-rms Clamp Instrukcja obsługi miernika
Kompleksowa instrukcja obsługi zdalnego wyświetlacza Fluke 381 True-rms Clamp Miernik. Obejmuje funkcje produktu, procedury pomiaru prądu przemiennego/stałego, objętościtage, rezystancja, częstotliwość, prąd rozruchowy, konserwacja, specyfikacje i informacje dotyczące bezpieczeństwa. Zawiera szczegółowe opisy diagramów i tabel.
Przedview Fluke 323/324/325 Clamp Instrukcja obsługi miernika
Kompleksowa instrukcja obsługi Fluke 323, 324 i 325 clamp mierniki, szczegółowe informacje o funkcjach, środkach ostrożności, specyfikacjach i wskazówkach operacyjnych umożliwiających dokładne pomiary elektryczne.
Przedview Instrukcja obsługi multimetru Fluke 116 True-rms
Instrukcja obsługi multimetru Fluke 116 True-rms, obejmująca informacje na temat funkcji, obsługi, bezpieczeństwa i danych technicznych.
Przedview Fluke 373 True-RMS AC Clamp Licznik - Dane techniczne i więcejview
Szczegółowe dane techniczne, kluczowe cechy, opis produktuview, specyfikacje i informacje dotyczące zamawiania miernika Fluke 373 True-RMS AC Clamp Miernik przeznaczony do pomiaru prądu przemiennego do 600 A.
Przedview Fluke 305 klamp Instrukcja obsługi miernika
User manual for the Fluke 305 Clamp Meter, providing detailed safety information, product specifications, and operational guidance for accurate electrical measurements.