Fieldpiece DR58

Fieldpiece DR58 Podgrzewany diodowy detektor wycieku czynnika chłodniczego Instrukcja obsługi

Model: DR58

1. Wprowadzenie

The Fieldpiece DR58 Heated Diode Refrigerant Leak Detector is an ultra-sensitive tool designed for HVACR professionals to quickly and accurately locate refrigerant leaks. Utilizing a heated diode sensor, it detects a wide range of refrigerants with high precision. This manual provides essential information for the proper setup, operation, maintenance, and troubleshooting of your DR58 leak detector.

Detektor wycieku czynnika chłodniczego z podgrzewaną diodą DR58

Image 1.1: The Fieldpiece DR58 Heated Diode Refrigerant Leak Detector, showing its main body and flexible probe.

2. Główne cechy

The DR58 is equipped with several features to enhance leak detection efficiency:

  • Ultra-Sensitive Heated Diode Sensor: Detects micro leaks as small as <0.03 oz/yr, offering 20 times greater sensitivity than traditional bubble methods.
  • Universal Refrigerant Compatibility: Capable of detecting all HFC, CFC, HCFC, HFO, H2N2 (Tracer Gas), and blended refrigerants used in HVACR systems.
  • Trwałe i długotrwałe: Features an IP54 rating for resistance against moisture and oil, ensuring reliability in various working conditions. The sensor has a typical life of 300 hours.
  • Clear Leak Indicators: A large, backlit LCD screen displays leak size and intensity using a bar graph and numeric readings. An LED tip and audible beep provide immediate feedback for precise leak pinpointing.
  • Flexible Probe and Extended Battery Life: A 17-inch flexible probe allows access to tight spaces. The rechargeable USB battery provides up to 18 hours of continuous operation. Replaceable filter tips are included.
Features and Benefits of Fieldpiece DR58

Image 2.1: Visual summary of the DR58's features, including its heated diode sensor, backlit LCD, refrigerant compatibility, and durable design.

3. Konfiguracja

Before initial use, ensure the DR58 is properly set up and charged.

3.1 Rozpakowanie i komponenty

Your Fieldpiece DR58 package should include:

  • 1 x Heated Diode Refrigerant Leak Detector (DR58)
  • 5 x Replacement Filtered Tips (RFT6)
  • 1 x Blow-Molded Case
  • 1 x Heated Diode Sensor (RHD1) (pre-installed or separate)
  • 1 x USB Charging Cable and Wall Adapter
What's Included with Fieldpiece DR58

Image 3.1: Contents of the DR58 package, showing the detector, charging cable, filter tips, and case.

3.2 Pierwsze ładowanie

  1. Connect the USB charging cable to the DR58's charging port.
  2. Plug the other end of the cable into the wall adapter and then into a power outlet.
  3. Allow approximately 6 hours for a full charge. The battery indicator on the LCD will show charging status.

3.3 Sensor and Filter Tip Installation

  1. Sprawdź, czy urządzenie jest wyłączone.
  2. If the heated diode sensor (RHD1) is not already installed, carefully insert it into the end of the flexible probe until it clicks into place.
  3. Screw a filtered tip onto the end of the sensor. Ensure it is finger-tight to prevent debris from entering the sensor.

4. Działanie

Follow these steps for effective leak detection with your DR58.

4.1 Powering On and Warm-up

  1. Press and hold the power button (blue button with sun icon) for approximately 1 second to turn on the device.
  2. The DR58 will display 'Warm' and then 'AZERO' as it warms up and performs an automatic zeroing. This process typically takes less than 10 seconds.

4.2 Zerowanie urządzenia

Zeroing establishes a baseline for the ambient air, allowing the detector to accurately identify refrigerant concentrations above this baseline.

  • Automatic Zeroing: The device automatically zeros upon power-on and continuously adjusts to background refrigerant levels during operation.
  • Manual Zeroing: To manually zero the device, move the probe to an area known to be free of refrigerant. Press the 'ZERO MANUAL/AUTO' button. The display will show 'AZERO' to confirm.

4.3 Regulacja czułości

The DR58 offers adjustable sensitivity levels to suit different leak detection scenarios.

  • Press the 'SENSITIVITY MAX ON/OFF' button to cycle through sensitivity levels (High, Medium, Low).
  • Use higher sensitivity for smaller leaks or when the leak source is difficult to pinpoint. Use lower sensitivity in areas with higher background refrigerant levels to avoid false positives.

4.4 Procedura wykrywania wycieków

  1. Slowly move the flexible probe along the suspected leak area, such as refrigerant lines, coils, and connections. Maintain a consistent speed of approximately 1-2 inches per second.
  2. Observe the LCD display for increasing bar graph segments and numeric readings, indicating the presence of refrigerant.
  3. Listen for the audible beep, which will increase in frequency and pitch as the leak source is approached.
  4. The LED tip on the probe will also illuminate red, intensifying as the leak concentration increases.
  5. Once a leak is detected, move the probe away from the area and then slowly re-approach to confirm the exact location.
DR58 probe tip with illuminated LED

Image 4.1: Close-up of the DR58's flexible probe tip, showing the illuminated red LED indicator during leak detection.

Video 4.1: An official product video demonstrating the Fieldpiece DR58 leak detector in use, highlighting its features and effectiveness in finding refrigerant leaks.

5. Konserwacja

Regular maintenance ensures the longevity and accuracy of your DR58.

5.1 Replacing Filter Tips

The filter tips prevent debris from entering the sensor. Replace them regularly, especially in dirty environments, or if they appear clogged.

  1. Unscrew the old filter tip from the sensor.
  2. Screw on a new replacement filter tip (RFT6) until it is finger-tight.

5.2 Wymiana czujnika

The heated diode sensor (RHD1) has a typical life of 300 hours. Replace the sensor when its performance degrades or if the device indicates a sensor error.

  1. Power off the DR58.
  2. Unscrew the filter tip.
  3. Gently pull the old sensor out of the probe.
  4. Insert the new RHD1 sensor into the probe until it clicks into place.
  5. Re-attach a clean filter tip.

5.3 Czyszczenie

  • Przetrzyj zewnętrzną powierzchnię urządzenia reklamąamp ściereczka. Nie należy używać środków czyszczących o właściwościach ściernych ani rozpuszczalników.
  • Ensure the sensor and filter tip are free from oil, moisture, and debris.

6. Rozwiązywanie Problemów

If you encounter issues with your DR58, refer to the following common problems and solutions.

ProblemMożliwa przyczynaRozwiązanie
Urządzenie nie włącza się.Niski poziom naładowania baterii lub jej rozładowanie.Charge the device using the provided USB cable and adapter.
Niedokładne lub niespójne odczyty.Sensor contaminated or worn out; filter tip clogged; high background refrigerant.Replace filter tip. Replace sensor if necessary. Perform manual zeroing in a clean air environment.
No leak detected despite suspected leak.Low sensitivity setting; probe moved too quickly; sensor issue.Increase sensitivity. Move probe slower. Check and replace sensor if needed.
Constant alarm or high readings in clean air.Device not properly zeroed; sensor contaminated.Perform manual zeroing in a clean air environment. Clean or replace sensor.

7. Specyfikacje

Technical specifications for the Fieldpiece DR58 Heated Diode Refrigerant Leak Detector.

Fieldpiece DR58 Specifications

Image 7.1: A detailed list of the DR58's technical specifications, including sensor type, sensitivity, and battery life.

SpecyfikacjaWartość
Typ czujnikaCzujnik z podgrzewaną diodą
Żywotność czujnikaTypowe godziny 300
Poziomy czułościWysoki, średni, niski (do wyboru)
Maksymalna czułość0.03 oz/yr (1g/a) stationary; 0.1 oz/yr (3g/a) in motion
Detection FeedbackCzerwona końcówka LED, wykres słupkowy LCD, cyfry LCD, brzęczyk
Czynniki chłodniczeHFC, HCFC, CFC, HFO i mieszanki
Czas reakcji<1 sekunda typowo
Czas regeneracji<10 sekunda typowo
Typ baterii3.7 VDC (nominalne) 2550 mAh, niewymienne
Czas ładowania6 hours typical with included charger
Żywotność bateriitypowo 18 godzin, podświetlenie wyłączone
Automatyczne wyłączanie zasilania10 minut bez wykrywania lub naciśnięcia przycisku
Środowisko operacyjne32°F do 104°F (0°C do 40°C); < 75% RH (bez kondensacji)
Temperatura przechowywania-4°F do 140°F (-20°C do 60°C); <80% wilgotności względnej
Waga14 uncji (400g)
Odporność na wodęZaprojektowany do IP54
Wymiary produktu10 x 8 x 10 cala

8. Gwarancja i wsparcie

Fieldpiece Instruments provides a warranty for its products against defects in material and workmanship. For specific warranty terms, registration, and technical support, please refer to the official Fieldpiece webOdwiedź stronę internetową lub skontaktuj się bezpośrednio z działem obsługi klienta. Zachowaj paragon jako dowód zakupu.

Aby uzyskać dalszą pomoc, odwiedź stronę Sklep Fieldpiece na Amazonie or the official Fieldpiece webstrona.

Powiązane dokumenty - DR58

PrzedviewInstrukcja obsługi detektora wycieków czynnika chłodniczego Fieldpiece DR58 z podgrzewaną diodą
Instrukcja obsługi detektora wycieków czynnika chłodniczego Fieldpiece DR58, szczegółowo opisana w niej: funkcje, specyfikacje, obsługa, instalacja, konserwacja i testowanie funkcjonalności w celu wykrywania różnych czynników chłodniczych.
PrzedviewInstrukcja obsługi detektora wycieków czynnika chłodniczego Fieldpiece DRX3
Kompleksowa instrukcja obsługi detektora wycieków czynnika chłodniczego Fieldpiece DRX3, szczegółowo opisująca jego funkcje, obsługę, środki ostrożności, konserwację i specyfikacje dla profesjonalistów HVAC.
PrzedviewInstrukcja obsługi detektora wycieków czynnika chłodniczego na podczerwień Fieldpiece DR82
Kompleksowy przewodnik po detektorze wycieków czynnika chłodniczego Fieldpiece DR82 na podczerwień, obejmujący jego funkcje, specyfikacje, obsługę, konserwację i gwarancję. Dowiedz się, jak wykrywać czynniki chłodnicze HFC, HCFC, CFC, HFO i mieszanki z wysoką czułością i wieloma wskaźnikami.
PrzedviewInstrukcja obsługi detektora wycieków czynnika chłodniczego na podczerwień Fieldpiece DR82
Operator's manual for the Fieldpiece DR82 Infrared (IR) Refrigerant Leak Detector. Details features, specifications, operation, maintenance, safety guidelines, and warranty information for HVACR professionals.
PrzedviewInstrukcja obsługi detektora wycieków czynnika chłodniczego na podczerwień Fieldpiece DR82
Kompleksowa instrukcja obsługi detektora wycieków czynnika chłodniczego Fieldpiece DR82 na podczerwień (IR), szczegółowo opisująca jego funkcje, obsługę, konserwację i specyfikacje dla profesjonalistów HVACR.
PrzedviewFieldpiece DRX3 Refrigerant Leak Detector Operator Manual
Comprehensive operator manual for the Fieldpiece DRX3 Refrigerant Leak Detector, detailing its features, operation, maintenance, and safety guidelines for detecting refrigerant and combustible gas leaks.