1. Wprowadzenie
The Elitech MTC-5060 is a digital temperature controller designed for precise temperature management in cold storage environments such as cold rooms and refrigerators. It features dual screens for simultaneous display of current and set temperatures, along with indicator lights for operational status. The controller supports both cooling and defrosting functions, offering comprehensive temperature control capabilities.
This manual provides detailed instructions for the installation, operation, and maintenance of your MTC-5060 temperature controller. Please read this manual thoroughly before installation and use to ensure proper function and safety.
2. Informacje dotyczące bezpieczeństwa
- Ensure the power supply matches the controller's specifications (110VAC±10%, 50Hz/60Hz).
- All wiring should be performed by a qualified electrician to prevent electric shock or damage to the unit.
- Do not operate the controller in environments with excessive humidity or corrosive gases.
- Przed przystąpieniem do prac konserwacyjnych lub okablowania należy odłączyć zasilanie.
- Kontroler przeznaczony jest wyłącznie do użytku wewnątrz pomieszczeń.
3. Funkcje produktu
- Podwójny wyświetlacz: Shows current room temperature and set temperature simultaneously.
- Cooling and Defrosting Control: Manages both refrigeration and defrosting cycles.
- Wysoka dokładność: Utilizes a high-precision sensor and chip for stable performance and minimal drift.
- Przyjazny dla użytkownika interfejs: Multi-functional button panel for easy parameter setting and operation.
- Funkcje alarmu: Includes high/low temperature alarm and sensor error alarm.
- EMC Standard Compliance: Passed industrial four-level tests for stable and reliable operation in harsh environments.

Rycina 3.1: Przód view of the Elitech MTC-5060 controller, illustrating the dual temperature display and control buttons.
4. Zawartość opakowania
Please check the package contents upon receipt. If any items are missing or damaged, contact your supplier immediately.
- Elitech MTC-5060 Digital Temperature Controller (1 unit)
- NTC Sensor Probe (1 unit)
- Instrukcja obsługi (1 kopia)
5. Instalacja i okablowanie
5.1 Montaż
The MTC-5060 controller is designed for panel mounting. Ensure adequate space for ventilation and access to wiring terminals.
- Rozmiar panelu przedniego: 10.2 cm (dł.) x 5.1 cm (szer.)
- Rozmiar produktu: 10.2 cm (dł.) x 5.1 cm (szer.) x 8.3 cm (gł.)
- Installing Hole Size: 9.2 cm (dł.) x 4.4 cm (szer.)

Figure 5.1: Physical dimensions of the MTC-5060 controller.

Figure 5.2: Required mounting hole dimensions for installation.
5.2 Schemat okablowania
Refer to the wiring diagram below for correct electrical connections. Ensure all connections are secure and comply with local electrical codes. The controller operates on 110VAC.

Figure 5.3: Wiring diagram for the MTC-5060 controller. Terminals 1-2 for power, 3-5 for sensors, 6-9 for output loads (cooling and defrosting).
- Zasilanie: Connect 110VAC to terminals 1 and 2.
- Połączenia czujnika: Connect the NTC sensor(s) to the designated terminals (e.g., 3, 4, 5). The MTC-5060 supports two sensors for storage temperature and defrosting temperature.
- Obciążenia wyjściowe: Connect cooling and defrosting loads to the respective relay output terminals (e.g., 7-8 for cooling, 8-9 for defrosting). The relay output contact capacity is 3A/110VAC.
6. Instrukcja obsługi
The MTC-5060 features a user-friendly interface with dedicated buttons for common functions and parameter settings.
6.1 Wyświetlacz i wskaźniki
The controller has two digital displays:
- Górny wyświetlacz: Pokazuje aktualną temperaturę pomieszczenia.
- Dolny wyświetlacz: Pokazuje ustawioną temperaturę.
Indicator lights provide visual feedback on the operating mode (e.g., cooling, defrosting).
6.2 Ustawianie temperatury
- Naciśnij Ustawić przycisk do view aktualnie ustawiona temperatura.
- While the set temperature is displayed, use the Up I W dół arrow buttons to adjust the desired temperature value.
- Naciśnij Ustawić button again to confirm and save the new setting.
6.3 Defrosting Control
The MTC-5060 supports automatic and manual defrosting.
- Automatyczne rozmrażanie: Configured through parameters (defrost cycle, defrost time). Refer to the detailed parameter settings section (if available in full manual) for adjustment.
- Odszranianie ręczne: Naciśnij Forced Def. button to initiate a manual defrost cycle.

Figure 6.1: Illustrates the "Forced Def." button for manual defrost initiation.
6.4 Ustawienia parametrów
Advanced parameters such as compressor delay, defrost cycle, defrost time, and temperature calibration can be accessed and adjusted. Consult the full product manual for a complete list of parameters and their functions.
Note: Incorrect parameter settings can affect the performance and safety of your refrigeration system. Proceed with caution when adjusting advanced settings.
7. Specyfikacje
| Parametr | Wartość |
|---|---|
| Zasilacz | 110VAC±10%, 50Hz/60Hz |
| Zakres pomiaru temperatury | -50°C do 50°C |
| Zakres regulacji temperatury | -50°C do 50°C |
| Dokładność | ±1°C |
| Rezolucja | 0.1°C |
| Relay Output Contact Capacity | 3A/110VAC |
| Temperatura pracy | 0°C do 60°C |
| Wilgotność względna | 20%-85% (bez kondensacji) |
| Typ czujnika | NTC (10KΩ/25°C, wartość B = 3435K) |
| Sensor Probe Length | 2 metrów (7.87 cala) |
| Rozmiar panelu przedniego | 10.2 cm (dł.) x 5.1 cm (szer.) |
| Wymiary produktu | 10.2 cm (dł.) x 5.1 cm (szer.) x 8.3 cm (gł.) |
| Installing Hole Size | 9.2 cm (dł.) x 4.4 cm (szer.) |
| Numer modelu | MTC-5060 |
| Producent | Elitarny |
8. Konserwacja
To ensure the longevity and optimal performance of your Elitech MTC-5060 controller, follow these maintenance guidelines:
- Czyszczenie: Regularly wipe the front panel with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Kontrola: Okresowo należy sprawdzać, czy wszystkie połączenia przewodów są dobrze dokręcone i czy nie ma śladów zużycia lub uszkodzenia.
- Kontrola czujnika: Ensure the temperature sensor is clean and properly positioned for accurate readings.
- Środowisko: Maintain the operating environment within the specified temperature and humidity ranges to prevent condensation and ensure reliable operation.
9. Rozwiązywanie Problemów
This section provides solutions to common issues you might encounter with your MTC-5060 controller.
| Problem | Możliwa przyczyna | Rozwiązanie |
|---|---|---|
| Kontroler nie włącza się. | Brak zasilania lub nieprawidłowe okablowanie. | Check power connections (terminals 1 & 2) and ensure 110VAC supply. Verify wiring against diagram. |
| Temperature display is inaccurate or shows "EE". | Sensor error or faulty sensor. | Check sensor connections. Ensure the sensor is not damaged. Replace sensor if necessary. Perform temperature calibration if readings are consistently off. |
| Cooling/Defrosting not activating. | Incorrect set temperature, parameter settings, or faulty output relay. | Verify set temperature and differential. Check relevant parameters (e.g., compressor delay, defrost cycle). Inspect wiring to the cooling/defrosting load. |
| High/Low temperature alarm triggers frequently. | Alarm limits set too close to operating temperature or actual temperature fluctuation. | Adjust high/low temperature alarm limits. Investigate the cause of temperature fluctuations in the controlled environment. |
Jeśli po wypróbowaniu tych rozwiązań problem nadal występuje, skontaktuj się z obsługą klienta Elitech w celu uzyskania dalszej pomocy.
10. Gwarancja i wsparcie
Elitech Technology, Inc. warrants this product to be free from defects in materials and workmanship for a period specified by your regional distributor from the date of purchase. This warranty does not cover damage caused by improper installation, misuse, unauthorized modification, or natural disasters.
For technical support, warranty claims, or service inquiries, please contact your local Elitech distributor or visit the official Elitech webwitryna do informacji kontaktowych.
Producent: Elitarny
Model: MTC-5060