DIGITEN FL-308

DIGITEN G3/8 Inch Quick Connect Water Flow Sensor Switch Flowmeter Counter FL-308 User Manual

Modele: FL-308

Wstęp

The DIGITEN G3/8 Inch Quick Connect Water Flow Sensor Switch (Model FL-308) is designed to measure water flow rates accurately. This device features quick connect fittings for easy installation and provides a pulse signal output proportional to the water flow. It is suitable for various applications requiring precise flow monitoring.

This manual provides essential information for the safe and effective installation, operation, and maintenance of your flow sensor.

Informacje dotyczące bezpieczeństwa

  • Upewnij się, że napięcie zasilaniatage is within the specified range (DC 3-24V) to prevent damage to the sensor.
  • Do not exceed the maximum water pressure of 0.8 MPa to avoid leaks or sensor failure.
  • Install the sensor in a location protected from extreme temperatures and humidity outside the specified operating ranges.
  • Zawsze odłączaj zasilanie przed przystąpieniem do prac instalacyjnych, okablowania lub konserwacji.
  • Handle the sensor with care to prevent physical damage.

Zawartość opakowania

  • 1 x DIGITEN G3/8" Water Flow Sensor (Model FL-308)

Prosimy o sprawdzenie zawartości przesyłki po jej otrzymaniu, aby upewnić się, że wszystkie elementy są obecne i nieuszkodzone. W przypadku braku lub uszkodzenia jakichkolwiek elementów prosimy o kontakt z obsługą klienta.

Specyfikacje

ModelFL-308
Zakres roboczy0.3 - 10 L/min
Objętość roboczatage ZakresDC 3 - 24 V
Maksymalny prąd10mA
Output Pulse RateF = 21 * Q (L/Min) ±2%
Przebieg wyjściowyFala kwadratowa
Zakres ciśnienia wody≤ 0.8 MPa
Temperatura pracy≤ 80℃
Wilgotność robocza35% - 90% wilgotności względnej
Temperatura przechowywania-25℃ - 80℃
Wilgotność przechowywania25% - 95% wilgotności względnej
TworzywoMiedź (elementy wewnętrzne)
Długość kabla15 cm
ZgodnośćZgodny z ROHS

Diagram showing the dimensions and features of the DIGITEN G3/8 Inch Water Flow Sensor FL-308, including watertight seal, wear-resistance, ROHS compliance, and high sensitivity.Figure 1: Product features and dimensions of the DIGITEN FL-308 Water Flow Sensor.

Konfiguracja i instalacja

1. Instalacja fizyczna

  1. Określ kierunek przepływu: The sensor has an arrow indicating the direction of water flow. Ensure the sensor is installed correctly in line with the water flow.
  2. Złączki połączeniowe: Use the G3/8 inch quick connect fittings to integrate the sensor into your water line. Ensure connections are secure and watertight to prevent leaks.
  3. Montowanie: Secure the sensor in a stable position to prevent movement or strain on the connections.

Z góry na dół view of the DIGITEN G3/8 Inch Water Flow Sensor FL-308, showing the quick connect fittings and the label with model number and wiring information.Rysunek 2: Góra view of the flow sensor with quick connect fittings.

Strona view of the DIGITEN G3/8 Inch Water Flow Sensor FL-308, highlighting the quick connect fitting and the compact design.Rysunek 3: Strona view of the flow sensor.

2. Instalacja elektryczna

The sensor comes with a 3-wire connection. Follow the wiring diagram below:

  • Czerwony przewód: Connect to VCC (+) (DC 3-24V power supply).
  • Czarny przewód: Connect to GND (Ground).
  • Żółty przewód: Connect to Signal Output (Pulse signal).

Z bliska view of the DIGITEN G3/8 Inch Water Flow Sensor FL-308, showing the wiring harness with red, black, and yellow wires connected to a white connector. The sensor label with wiring instructions is clearly visible.Figure 4: Wiring connections for the flow sensor.

Aby zapobiec zwarciom i zagrożeniom elektrycznym, należy upewnić się, że wszystkie połączenia elektryczne są solidne i właściwie zaizolowane.

Instrukcja obsługi

The DIGITEN FL-308 water flow sensor operates based on the Hall effect principle, generating a square wave pulse signal proportional to the water flow rate.

Flow Rate Calculation

The output frequency (F) in Hz can be calculated using the following formula:

F = 21 * Q (L/Min)

Gdzie:

  • F is the output pulse frequency in Hz.
  • Q is the water flow rate in Liters per Minute (L/Min).

The sensor provides approximately 450 output pulses per liter of water. This value can be used for total volume measurement over time.

Connect the yellow signal wire to a microcontroller or a pulse counter to read the frequency and calculate the flow rate or total volume.

Konserwacja

  • Regularna kontrola: Periodically check the sensor and its connections for any signs of wear, damage, or leaks.
  • Czyszczenie: If the sensor's performance degrades, it may be due to debris accumulation. Disconnect the sensor from the water line and power, then carefully flush it with clean water. Avoid using harsh chemicals.
  • Składowanie: If storing the sensor for an extended period, ensure it is clean, dry, and stored within the specified storage temperature and humidity ranges.

Rozwiązywanie problemów

ProblemMożliwa przyczynaRozwiązanie
Brak sygnału wyjściowego
  • Incorrect wiring (VCC, GND, Signal).
  • Brak zasilania lub nieprawidłowa głośnośćtage.
  • Sensor blockage or damage.
  • Sprawdź połączenia okablowania zgodnie ze schematem.
  • Check power supply and ensure it's within DC 3-24V.
  • Inspect the sensor for physical damage or internal blockage.
Inaccurate flow readings
  • Air bubbles in the water line.
  • Sensor installed against flow direction.
  • Debris inside the sensor.
  • Zewnętrzne zakłócenia elektromagnetyczne.
  • Ensure water line is free of air.
  • Re-install sensor according to flow direction arrow.
  • Clean the sensor as described in the Maintenance section.
  • Relocate sensor away from strong electromagnetic fields.
Wyciek wody
  • Loose quick connect fittings.
  • Uszkodzone pierścienie uszczelniające lub uszczelki.
  • Exceeded maximum pressure.
  • Ensure fittings are fully seated and secure.
  • Inspect and replace any damaged seals.
  • Verify water pressure is below 0.8 MPa.

Gwarancja i wsparcie

DIGITEN provides a one-year warranty for any quality problems with this product. For technical support, troubleshooting assistance, or warranty claims, please contact DIGITEN customer service through the retailer where the product was purchased or visit the official DIGITEN webstrona.

Proszę zachować paragon jako dowód zakupu w celach gwarancyjnych.

© 2026 DIGITEN. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.