DIGITEN G1 Water Flow Sensor (Model FL-808) Instruction Manual

Model: FL-808 | Brand: DIGITEN

Wstęp

This manual provides detailed instructions for the installation, operation, and maintenance of the DIGITEN G1 Water Flow Sensor, Model FL-808. This Hall effect flow sensor is designed for accurate measurement of liquid flow within a range of 1 to 60 liters per minute. Please read this manual thoroughly before use to ensure proper function and safety.

Produkt ponadview

The DIGITEN G1 Water Flow Sensor (Model FL-808) is a robust and reliable device for measuring water flow. It features G1 (0.5 inch) threaded connections for easy integration into various systems. The sensor outputs a square wave pulse signal proportional to the flow rate, making it suitable for microcontrollers and other electronic systems.

Główne cechy:

  • Trwała konstrukcja: Waterproof, heat-resistant, pressure-resistant, and cold-resistant design.
  • Szeroki zakres przepływu: Measures flow from 1 to 60 Liters per minute.
  • Łatwa instalacja: Simple G1 (0.5 inch) threaded connections.
  • Wyjście impulsowe: Generates a square wave pulse signal for flow rate calculation.
  • Zgodność z RoHS: Spełnia normy środowiskowe.

Informacje dotyczące bezpieczeństwa

  • Przed instalacją lub konserwacją należy upewnić się, że zasilanie jest odłączone.
  • Nie przekraczać maksymalnego ciśnienia roboczego wynoszącego 1.75 MPa.
  • Verify correct wiring connections to prevent damage to the sensor or connected equipment.
  • Avoid installing the sensor in locations with extreme vibrations or corrosive environments.
  • This device is intended for water flow measurement. Do not use with other liquids without verifying compatibility.

Zawartość opakowania

  • 1 x DIGITEN G1 Water Flow Sensor (Model FL-808)

Dane techniczne

ModelFL-808
TworzywoMetal (Internal components), Plastic (Housing)
Rozmiar przyłącza wlotowego/wylotowegoG1 (0.5 inch) Threaded
Zakres natężenia przepływu1 - 60 L/min
Maksymalne ciśnienie robocze1.75 MPa (17.5 bar)
Objętość operacyjnatage ZakresDC 5 - 24 V
Prąd roboczyCannot exceed 10 mA (at DC 5V)
Sygnał wyjściowySquare Wave Pulse
Frequency FormulaF = 4.8 * Q (L/min) ± 2%
Output Pulse per LiterApproximately 450 pulses/liter
Temperatura pracy≤ 80°C
Wilgotność robocza35% - 90% wilgotności względnej
Temperatura przechowywania-25°C do +80°C
Wilgotność przechowywania25% - 95% wilgotności względnej
Rezystancja izolacji> 100 MΩ
Długość kabla15 cm
Waga produktu80 gramów

Konfiguracja i instalacja

1. Instalacja mechaniczna

The flow sensor features G1 (0.5 inch) male threaded connections on both ends. Ensure the flow direction arrow on the sensor body aligns with the intended water flow in your system. Apply appropriate thread sealant (e.g., PTFE tape) to prevent leaks. Tighten connections securely but do not overtighten.

DIGITEN G1 Water Flow Sensor, front view

Rycina 1: Przód view of the DIGITEN G1 Water Flow Sensor, showing the G1 threaded connections and the product label.

Technical drawing of DIGITEN G1 Water Flow Sensor with dimensions

Figure 2: Technical drawing illustrating the dimensions and internal structure of the DIGITEN G1 Water Flow Sensor.

2. Instalacja elektryczna

The sensor has a 3-wire connection. Connect the wires as follows:

  • Czerwony przewód: VCC (+) - Connect to DC 5V to 24V power supply.
  • Czarny przewód: GND (-) - Connect to ground.
  • Żółty przewód: Signal Output - Connect to your microcontroller or data acquisition system's input pin.

Upewnij się, że objętość roboczatage is within the specified range of DC 5-24V. The current drawn by the sensor should not exceed 10mA at 5V DC.

DIGITEN G1 Water Flow Sensor with red, black, and yellow wires connected

Rysunek 3: Zbliżenie view of the sensor's wiring connections: Red (VCC), Black (GND), and Yellow (Signal).

Close-up of the 3-pin connector for the DIGITEN G1 Water Flow Sensor

Rysunek 4: Szczegółowy view of the 3-pin connector attached to the sensor's cable.

Instrukcja obsługi

Zasada działania

The DIGITEN G1 Water Flow Sensor uses a Hall effect sensor to detect the rotation of an internal turbine. As water flows through the sensor, it spins a turbine, and a magnet attached to the turbine generates a series of electrical pulses. The frequency of these pulses is directly proportional to the flow rate of the water.

Flow Rate Calculation

The output signal is a square wave. The flow rate (Q in L/min) can be calculated from the measured frequency (F in Hz) using the following formula:

F = 4.8 * Q (L/min)

Therefore, to find the flow rate:

Q (L/min) = F / 4.8

The sensor provides approximately 450 pulses per liter of water. The accuracy is ±2%.

DIGITEN G1 Water Flow Sensor showing internal turbine

Rysunek 5: Wewnętrzne view of the sensor, highlighting the turbine mechanism responsible for pulse generation.

DIGITEN G1 Water Flow Sensor with clear label and connections

Figure 6: The sensor with its label clearly visible, detailing model number, working range, and wiring information.

Konserwacja

  • Regularna kontrola: Periodically check for any signs of leaks at the connections or damage to the sensor body and wiring.
  • Czyszczenie: If the sensor's accuracy degrades, it may be due to debris accumulation inside the turbine. Disconnect power and water supply, then carefully remove the sensor for inspection and cleaning. Use a soft brush and clean water to remove any obstructions.
  • Składowanie: If storing the sensor for an extended period, ensure it is clean, dry, and kept within the specified storage temperature and humidity ranges (-25°C to +80°C, 25%-95% RH).

Rozwiązywanie problemów

ProblemMożliwa przyczynaRozwiązanie
Brak sygnału wyjściowego
  • Incorrect wiring (VCC, GND, Signal)
  • Brak zasilania
  • Awaria czujnika
  • Brak przepływu wody
  • Check wiring against the diagram.
  • Verify power supply (DC 5-24V) is connected and active.
  • Ensure water is flowing through the sensor.
  • Test with a known good sensor if possible.
Inaccurate flow readings
  • Debris inside the sensor
  • Air bubbles in the water line
  • Incorrect frequency calculation formula
  • Sensor installed incorrectly (e.g., against flow direction)
  • Clean the sensor as described in the Maintenance section.
  • Bleed air from the water system.
  • Double-check the calculation formula (F = 4.8 * Q).
  • Verify the flow direction arrow on the sensor.
Wycieki na połączeniach
  • Niewystarczająca ilość uszczelniacza gwintów
  • Luźne połączenia
  • Uszkodzone gwinty
  • Reapply thread sealant (PTFE tape) and retighten.
  • Ensure connections are snug.
  • Inspect threads for damage; replace if necessary.

Gwarancja i wsparcie

For warranty information or technical support, please contact DIGITEN customer service through the retailer where the product was purchased or visit the official DIGITEN website. Please have your product model number (FL-808) and purchase details ready when contacting support.

© 2023 DIGITEN. All rights reserved.