Fulham FHS2-UNV-36L

Instrukcja obsługi awaryjnego sterownika LED Fulham FHS2-UNV-36L

1. Wprowadzenie

This manual provides essential instructions for the safe installation, operation, and maintenance of the Fulham FHS2-UNV-36L Emergency LED Driver. This device is designed to provide emergency power to LED luminaires in the event of a normal power failure, ensuring illumination for a specified duration. Please read this manual thoroughly before installation or use and retain it for future reference.

2. Informacje dotyczące bezpieczeństwa

OSTRZEŻENIE: To reduce the risk of death, personal injury, or property damage from fire, electric shock, falling parts, cuts, abrasions, and other hazards, read all warnings and instructions included with and on the fixture box and all fixture labels. All electrical work must be performed by a qualified electrician in accordance with all applicable national and local electrical codes.

  • Przed przystąpieniem do instalacji lub serwisowania należy odłączyć zasilanie przy bezpieczniku lub wyłączniku automatycznym.
  • Upewnij się, że głośność wejściowatage to the emergency driver matches the specified range (100-277V AC).
  • Nie instaluj w pobliżu grzejników gazowych lub elektrycznych.
  • Nie używaj tego sprzętu niezgodnie z jego przeznaczeniem.
  • This product is designed for use with specific LED loads. Refer to specifications for compatibility.
  • The emergency driver requires a separate battery backup unit (not included) for emergency operation. Ensure the battery unit is compatible and correctly installed.
Label on Fulham Emergency LED Driver showing electrical ratings and warnings.
Rysunek 2.1: Product label displaying electrical ratings and important safety warnings. This label emphasizes the need to consult the instruction manual for complete installation, operating, and maintenance procedures before AC power is supplied to the unit.

3. Koniec produktuview

The Fulham FHS2-UNV-36L is an emergency LED driver designed to convert standard LED luminaires into emergency lighting fixtures. It provides constant power output to the LED load during a power outage, ensuring continuous illumination for a minimum of 90 minutes. This unit operates with a universal input voltage range and is suitable for various commercial and industrial applications.

  • Model: FHS2-UNV-36L
  • Funkcjonować: Awaryjny sterownik LED
  • Czas trwania sytuacji awaryjnej: Minimum 90 minut
  • Wejście Voltage: 100-277V AC
  • Objętość wyjściatage: 11-36V DC
  • Maksymalna moc wyjściowa: 20 watów
  • Zapas baterii: Not included (requires external battery pack)
Fulham FHS2-UNV-36L Emergency LED Driver with wiring.
Rysunek 3.1: The Fulham FHS2-UNV-36L Emergency LED Driver (right) shown with its associated wiring. This image illustrates the compact form factor and the various wire connections required for installation, including connections to an external battery pack (left, FHSBATL6-3) and the LED load.

4. Konfiguracja i instalacja

Installation must be performed by a qualified electrician in compliance with all national and local electrical codes. Ensure power is disconnected before beginning any installation work.

4.1 instrukcje okablowania

  1. Odłączenie zasilania: Turn off the main power supply to the circuit where the emergency driver will be installed. Verify power is off using a voltagtester.
  2. Montowanie: Mount the FHS2-UNV-36L emergency driver securely within the fixture or in an accessible location, ensuring proper ventilation. The unit has a rectangular aluminum housing.
  3. Podłączenie wejścia AC: Connect the AC input wires of the emergency driver to the unswitched AC power supply (100-277V). Typically, this involves connecting the black wire to Line, white wire to Neutral, and green wire to Ground.
  4. Podłączenie akumulatora: Connect the emergency driver to a compatible external battery backup unit (e.g., Fulham FHSBATL6-3, if applicable). Ensure correct polarity (positive to positive, negative to negative). The product description states the battery backup is not included with the FHS2-UNV-36L.
  5. LED Load Connection: Connect the output wires of the emergency driver to the LED load. Observe correct polarity for the LED module. The output voltagZakres wynosi 11-36 V DC.
  6. Test Switch/Indicator: If applicable, connect the test switch and charge indicator light according to the wiring diagram provided with the battery backup unit. This allows for manual testing of the emergency function.
  7. Przywrócenie zasilania: Once all connections are secure and verified, restore power to the circuit. The charge indicator light should illuminate, indicating the battery is charging.

Note: Always refer to the specific wiring diagram provided with your complete emergency lighting system for detailed connection instructions.

5. Instrukcja obsługi

The Fulham FHS2-UNV-36L Emergency LED Driver operates automatically. No user intervention is required during normal operation or during a power outage.

  • Tryb normalny: When AC power is present, the emergency driver's battery unit (if connected) will charge. The LED luminaire operates normally, powered by the standard AC supply.
  • Tryb awaryjny: Upon interruption of normal AC power, the emergency driver automatically switches to emergency mode. It draws power from the connected battery backup unit and supplies power to the LED load, illuminating the fixture for a minimum of 90 minutes.
  • Powrót do normy: When AC power is restored, the emergency driver automatically returns to normal mode, and the battery unit begins recharging.

5.1 Testing Emergency Function

Regular testing is crucial to ensure the emergency lighting system is functioning correctly.

  1. Test miesięczny: Press the test switch (if installed) for at least 30 seconds. The LED luminaire should operate in emergency mode. Release the switch; the luminaire should return to normal operation.
  2. Test roczny: Conduct a full 90-minute discharge test annually. Disconnect AC power to the emergency driver for 90 minutes. The LED luminaire should remain illuminated for the entire duration. After the test, restore AC power and allow the battery to fully recharge (typically 24 hours).

6. Konserwacja

The Fulham FHS2-UNV-36L Emergency LED Driver is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance.

  • Czyszczenie: Utrzymuj urządzenie w czystości, bez kurzu i zanieczyszczeń. Do czyszczenia używaj suchej, miękkiej ściereczki. Nie używaj płynnych środków czyszczących.
  • Kontrola: Periodically inspect the wiring for any signs of damage, loose connections, or corrosion.
  • Wymiana baterii: The lifespan of the external battery backup unit varies. If the unit fails to maintain illumination for the full 90-minute duration during an annual test, the battery may need replacement. Refer to the battery manufacturer's instructions for replacement procedures.

7. Rozwiązywanie Problemów

If the emergency LED driver is not functioning as expected, refer to the following troubleshooting guide:

ProblemMożliwa przyczynaRozwiązanie
LED luminaire does not illuminate in emergency mode.No AC power to the emergency driver.
Battery not charged or faulty.
Nieprawidłowe okablowanie.
Faulty LED load.
Sprawdź wyłącznik automatyczny i połączenia przewodów.
Allow 24 hours for battery to charge. If problem persists, replace battery.
Sprawdź wszystkie połączenia okablowania zgodnie ze schematem.
Test LED load with a known good power source.
Emergency illumination duration is less than 90 minutes.Akumulator nie jest w pełni naładowany.
Akumulator zbliża się do końca żywotności.
Incompatible LED load.
Ensure battery has had sufficient time to charge (24 hours).
Replace the battery backup unit.
Verify LED load specifications are within the driver's output range.
Kontrolka ładowania jest wyłączona.No AC power to the emergency driver.
Faulty indicator light or wiring.
Akumulator nie podłączony.
Sprawdź zasilanie prądem zmiennym.
Inspect indicator light and its connections.
Sprawdź, czy akumulator jest prawidłowo podłączony.

If troubleshooting steps do not resolve the issue, contact Fulham customer support or a qualified electrician.

8. Specyfikacje

FunkcjaSpecyfikacja
Numer modeluFHS2-UNV-36L
Wejście Voltage100-277V AC
Objętość wyjściatage11-36V DC
Maksymalna moc wyjściowa20 watów
Ampwymazać0.07 Amps
Czas pracy awaryjnejMinimum 90 minut
Wymiary (dł. x szer. x wys.)10.25" x 1.5" x 1.25" (26.04 cm x 3.81 cm x 3.18 cm)
Waga9.9 uncji (0.28 kg)
TworzywoAluminium
Typ montażuMontaż w stojaku
Bateria w zestawieNIE
UPC847098011026

9. Gwarancja i wsparcie

Fulham products are manufactured to high-quality standards and are backed by a manufacturer's warranty. For specific warranty terms and conditions, please refer to the warranty statement provided with your purchase or visit the official Fulham website. For technical support, troubleshooting assistance, or to inquire about replacement parts, please contact Fulham customer service.

Fulham Contact Information:
Proszę odwiedzić www.fulham.com Aby uzyskać najnowsze dane kontaktowe i zasoby pomocy.

© 2023 Fulham. All rights reserved. Information subject to change without notice.