Flowline DL10-01

Flowline DL10-01 EchoPod Ultrasonic Level Transmitter Instruction Manual

Model: DL10-01

1. Wprowadzenie

The Flowline DL10-01 EchoPod Ultrasonic Level Transmitter is a general-purpose, non-contact liquid level sensor designed for continuous level measurement. It provides a 4-20 mA signal output and is suitable for various applications involving corrosive, sticky, or dirty liquids. This manual provides essential information for the proper installation, operation, and maintenance of your DL10-01 EchoPod transmitter.

Flowline DL10-01 EchoPod Ultrasonic Level Transmitter

Image showing the Flowline DL10-01 EchoPod Ultrasonic Level Transmitter, a compact device with a 1-inch NPT process mount and integrated cable.

2. Koniec produktuview

The DL10-01 EchoPod offers reliable level measurement through ultrasonic technology. Key features include:

  • Continuous Non-Contact Measurement: Measures liquid levels up to 49.2 inches (1.25 meters) without physical contact with the medium.
  • Wyjście 4-20 mA: Provides a standard industrial signal for integration with control systems, supporting distances up to 1000 feet (300 meters).
  • WebCal Software Configuration: Easy setup and calibration using the free WebCal software and a USB adapter (Fob).
  • Zoptymalizowany projekt: Features a narrow 2-inch beam width and a short 2-inch dead band, making it suitable for small tanks.
  • Odporność na korozję: Constructed with a PVDF transducer and a Type 6P polycarbonate enclosure, ensuring durability in corrosive environments.
  • Automatyczna kompensacja temperatury: Ensures accurate measurements across varying process temperatures.

The device includes a 48-inch (1.2m) 4-conductor shielded polyurethane cable for connection.

3. Konfiguracja i instalacja

3.1 Montaż

The DL10-01 EchoPod features a 1-inch NPT process mount. Ensure the mounting location provides a clear, unobstructed path for the ultrasonic beam to the liquid surface. Use the provided Viton gasket to ensure a proper seal during installation.

3.2 Okablowanie

The transmitter operates on a 24 VDC loop power supply. It is a two-wire device with a 4-20 mA signal output. Connect the 4-conductor shielded cable according to the wiring diagram provided in the full product documentation. Ensure proper polarity and secure connections to prevent signal interference.

3.3 Konfiguracja

Configuration of the DL10-01 is performed using the WebCal PC Windows software and a USB 2.0 adapter (Fob). This Fob is essential for setting parameters such as range, signal invert (4-20 mA or 20-4 mA), and signal fail-safe options (4 mA, 20 mA, 21 mA, 22 mA, or hold last). Connect the Fob to your PC and the transmitter to access the configuration interface.

The device features non-volatile memory, retaining settings even after power loss. Automatic temperature compensation is integrated to maintain measurement accuracy.

4. Instrukcja obsługi

Once properly installed and configured, the DL10-01 EchoPod continuously emits ultrasonic pulses towards the liquid surface. The time it takes for these pulses to return is used to calculate the liquid level. This measurement is then converted into a 4-20 mA current signal, which can be read by a PLC, DCS, or other control system.

  • Wyjście sygnału: The output signal directly corresponds to the measured liquid level, as configured in WebWapno
  • Tryb awaryjny: In the event of a measurement error or loss of signal, the transmitter will output the pre-configured fail-safe current (e.g., 4 mA, 20 mA, 21 mA, 22 mA, or hold last value).
  • Monitorowanie: Regularly monitor the output signal and compare it with known liquid levels to ensure accurate operation.

5. Konserwacja

The Flowline DL10-01 EchoPod is designed for minimal maintenance due to its non-contact measurement principle and robust construction.

  • Czyszczenie: Periodically inspect the transducer face for any buildup of dirt, scale, or other contaminants. Clean gently with a soft cloth and mild detergent if necessary. Avoid abrasive materials that could damage the PVDF transducer.
  • Integralność obudowy: Ensure the Type 6P polycarbonate enclosure remains sealed and free from damage to maintain its submersible and corrosion-resistant properties.
  • Kontrola kabla: Check the polyurethane cable for any signs of wear, cuts, or damage. Replace if integrity is compromised.

No internal user-serviceable parts are present. Refer all repairs to qualified personnel.

6. Rozwiązywanie Problemów

This section addresses common issues you might encounter with the DL10-01 EchoPod transmitter.

6.1 Noisy or Erratic Signal

  • Przyczyna: Environmental interference, obstructions in the beam path, or temporary software/firmware glitch.
  • Rozwiązanie:
    1. Inspect the tank for any new obstructions or changes in the liquid surface that might interfere with the ultrasonic beam.
    2. Check for strong air currents or foam on the liquid surface.
    3. Disconnect and reconnect the power to the sensor to perform a "reboot." This can resolve temporary glitches.
    4. Verify wiring connections for looseness or corrosion.
    5. Użyj WebCal software to check diagnostic information and re-calibrate if necessary.

6.2 No Output Signal

  • Przyczyna: No power, incorrect wiring, or sensor failure.
  • Rozwiązanie:
    1. Verify that 24 VDC power is supplied to the transmitter.
    2. Check all wiring connections for correctness and integrity.
    3. Ensure the Fob is not connected during normal operation, as it is for configuration only.
    4. Jeśli problem będzie się powtarzał, skontaktuj się z pomocą techniczną.

6.3 Configuration Issues (Fob Related)

  • Przyczyna: Missing or faulty USB adapter (Fob), incorrect WebCal software installation, or driver issues.
  • Rozwiązanie:
    1. Ensure you have the correct Flowline USB adapter (Fob) for configuration.
    2. Sprawdź, czy WebCal software is correctly installed on your PC and that the necessary USB drivers are present.
    3. Try connecting the Fob to a different USB port or another computer.

7. Specyfikacje

Parametr Wartość
Zakres pomiaru 49.2 cale (1.25 metra)
Dokładność 0.125 cala (3 mm)
Rezolucja 0.019 cala (0.5 mm)
Martwy zespół 2 cali (5 cm)
Szerokość wiązki 2 cali (5 cm)
Konfiguracja WebCal PC Windows USB 2.0 (requires Fob)
Pamięć Nieulotny
Objętość dostawtage 24 VDC (loop)
Konsumpcja 0.5 W
Odporność na pętle 400Ω maximum
Wyjście sygnału 4-20 mA, two-wire
Signal Invert 4-20 mA lub 20-4 mA
Signal Fail-Safe 4 mA, 20 mA, 21 mA, 22 mA or hold last
Temperatura procesu od -20 do 140°C (od 7 do 60°F)
Temperatura otoczenia -31 do 140°F (-35 do 60°C)
Kompensacja temperatury Automatyczny
Ciśnienie (MWP) 30 psi (2 bara)
Stopień ochrony obudowy Type 6P, encapsulated, corrosion resistant and submersible
Materiał obudowy Poliwęglan
Transducer Material PVDF
Typ kabla 4-conductor, shielded
Długość kabla 48 cale (1.2 metra)
Process Mount 1 cal NPT
Mount Gasket Witon
Klasyfikacja Ogólne zastosowanie
Zgodność CE, RoHS
Zatwierdzenia cFMus
Wymiary produktu 7.5 x 7 x 2.3 cala
Waga przedmiotu 7 uncji

8. Gwarancja i wsparcie

For specific warranty information regarding your Flowline DL10-01 EchoPod Ultrasonic Level Transmitter, please refer to the documentation provided at the time of purchase or contact your authorized Flowline distributor or the manufacturer directly. Warranty terms typically cover defects in materials and workmanship for a specified period.

For technical support, troubleshooting assistance beyond this manual, or inquiries about replacement parts, please contact Flowline customer service or your local distributor. Ensure you have your product model number (DL10-01) and any relevant purchase details available when seeking support.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.